Liebert GXT4 is a true on-line UPS that delivers continuous, high-quality AC power to IT equipment with no break when transferring to battery. It protects equipment from virtually all power disturbances due to blackouts, brownouts, sags, surges or noise interference.
For robust protection from 500-10,000VA, these Liebert GXT4 UPS models provide industry leading features in a compact design.
Configuration | Tower or Rack-mounted |
Warranty | 2-years (1 or 3 year extension available) |
Model Contents | (ships with the following items included) |
Liebert GXT4 2000VA UPS | |
4-post Rack-mounting Rail Kit | |
Tower Support Stands | |
(3) 10A, IEC320-C13 to IEC320-C14 Output Power Cables (6.5 feet) | |
(1) 16A, CEE 7/7 (Shucko) to IEC320-C19 Input Power Cable (8.5 feet) | |
(1) 16A, BS 1363 (UK) to IEC320-C19 Input Power Cable (8.5 feet) | |
(1) 16A, Australian Type A to IEC320-C19 Input Power Cable (8.5 feet) | |
USB Cable (3.9 feet) | |
Quick Start Guide | |
UPS Configuration Program (Installation CD) | |
POWER OUTPUT | |
---|---|
Output Connections | Quantity (6) |
Output Power Capacity | 2000 VA / 1800 Watts |
Power Factor | 0.9 |
Nominal Output Voltage | 230V (200V / 208V / 220V / 230V / 240V also available) |
Output Voltage Distortion | 3% THDv for Linear Loads, 5% THDv for Non-linear loads |
Output Frequency | 50Hz / 60Hz |
Output Frequency Range | '+/- 3 Hz |
Crest Factor | 3:1 |
UPS Topology | Online Double-Conversion |
Output Waveform | Sine-wave |
Load Power Factor Range | 0.65 lagging to 1.0 (unity) without derating |
Bypass | Built-in Bypass |
POWER INPUT | |
Nominal Input Voltage | 230V (200V / 208V / 220V / 230V / 240V also available) |
Input Voltage Range | 177 - 280V @ rated load; 115 - 280V, load dependent |
Input Frequency | 40 - 70 Hz |
Input Power Factor | 0.99 |
Reflected Input Current Distortion | 5% THDi |
Input Connections | input socket |
Circuit Protection | Circuit Breaker |
BACKUP RUNTIME / BATTERIES | |
Battery Type | Maintenance-free sealed Lead-Acid battery: leakproof |
Replacement Battery | GXT4-9A48BATKIT |
Typical Re-charge Time | 5 hours to 90% capacity |
Extended Run Options | Up to 6 External Battery Cabinets (P/N: GXT4-48VBATT) |
Backup Runtime in minutes (Full load / Half Load) | 3 / 12 |
ENERGY USE / EFFICIENCY | |
Energy Saving Mode (Eco-Mode) | User Selectable and Configurable |
Energy Star Qualified | Yes |
COMMUNICATIONS AND MANAGEMENT | |
Control Panel | LCD status / configuration display |
LED Status | Yes, On Inverter, On Bypass, On Battery, Fault, ECO Mode, Outlet Groups On/Off |
Output Receptable Control | (2) Programmable / Controllable Outlet Groups |
Interface Port(s) | (1) IntelliSlot, (1) USB port Type B, (1) DB9F |
Available IntelliSlot Quantity | 1 (SNMP, 485, Relay interface cards available) |
Contact Interfaces | (4) Contacts (on battery, low battery, anymode shutdown, battery mode shutdown) |
Emergency Power Off (EPO) | Using Any-mode Shutdown contact |
Audible Alarm | Yes, user can disable |
Power Management Software | Liebert Multilink Shutdown Software (Installation CD included) |
SURGE PROTECTION AND FILTERING | |
Surge Energy Rating | 80 Joules |
Filtering | Full time noise filtering, meets IEEE C62.41 Cat. A, Level 3 and FCC Part A |
PHYSICAL | |
UPS Dimensions (Rack Orientation) | Width: 16.9 inches, Height: 3.4 inches, Depth: 19.6 inches |
Rack Height Units | 2U |
UPS Dimensions (Tower Orientation) | Width: 3.4 inches, Height: 16.9 inches, Depth: 19.6 inches |
UPS Weight | 56.1 pounds |
Shipping Dimensions (Packaging) | Width: 10.6 inches, Height: 22.4 inches, Depth: 24.3 inches |
Shipping Weight | 70.5 pounds |
Units per Pallet | 16 |
ENVIRONMENTAL | |
Operating Environment | 32 - 104 °F (0 - 40 °C) |
Operating Relative Humidity | 0 - 95% non-condensing |
Operating Elevation | 10,000 feet (3,000 meters) without derating |
Storage Temperature | 5 - 122 °F (-15 - 50 °C) |
Storage Elevation | Per IEC62040-3, suitable for transportation in pressurized aircraft |
Sound Emission | 48 dBA front & sides & rear |
Online Thermal Dissipation | 600 BTU/Hr @ Full Load |
Protection Class | IP 20 |
CONFORMANCE / STANDARDS | |
Compliant Standards | CE, GS, C-tick, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, IEC 62040-2, CISPR 22 Class B |
RoHS Compliance | Yes |
REACH Compliance | Yes |